Anhydrous Ammonia Release at Industrial Facility

Ellington, Connecticut

Facility and Industry Description

Industrial operations utilizing anhydrous ammonia in Ellington, Connecticut function within the closed-loop mechanical refrigeration or agricultural storage sectors. Anhydrous ammonia serves as an efficient refrigerant due to its high latent heat of vaporization, yet operating pressures frequently range from 150 to 250 psig under ambient summer condenser conditions.

Incident Summary

Emergency response agencies in Ellington mobilized following a reported loss of primary containment that discharged an unspecified amount of anhydrous ammonia into the atmosphere. The release produced a localized vapor plume characterized by the dense aerosol formation typical of pressurized liquid flashes at standard atmospheric pressure. Emergency crews established an isolation perimeter downwind to mitigate community exposure

Potentially Applicable Standards

  • Compliance with ANSI/IIAR 2 Chapter 13 requires mechanical refrigeration machinery rooms to maintain continuous vapor detection set to trigger emergency mechanical exhaust ventilation at 1,000 ppm while initiating audible alarms at 25 ppm.

  • Implementation of ANSI/IIAR 6 establishes mandatory schedules for nondestructive testing, visual inspection of insulated pipe segments for corrosion under insulation (CUI), and regular relief valve recertification every five years.

Top Three Sources

  1. Connecticut Department of Energy and Environmental Protection (DEEP) Emergency Response Unit Public Records

  2. Ellington Volunteer Fire Department Incident Response Reports

  3. Occupational Safety and Health Administration (OSHA) Region 1 Establishment Enforcement Database

Previous
Previous

Munitions Facility Explosion

Next
Next

Steam Header Rupture and Emergency Flaring at Petroleum Refinery